Reference
Plugs, sockets, and what each one will carry
A UK show runs on half a dozen connector families, and most of the trouble I see comes from treating a 13 A plug as a socket you can lean on all night, assuming one blue powerCON is the same as the next, and adaptors that remove the protection the circuit was designed with. Below are the ratings from the datasheets and standards, the arithmetic that turns them into kilowatts, and the combinations I keep finding plugged into each other.
The short version
| Connector | Standard | Rating | At rating | Sealing | Cable you'll usually see |
|---|---|---|---|---|---|
| IEC C13/C14 | IEC 60320-1 | 10 A | 2.30 kW230 V | none | 1.0 mm² (0.75 short) |
| BS 1363 13 A plug | BS 1363 | 13 A | 2.99 kW230 V | none | 1.25–1.5 mm² |
| IEC C19/C20 | IEC 60320-1 | 16 A | 3.68 kW230 V | none | 1.5 mm² |
| powerCON XX, blue/grey | EN 60320-1 | 16 A | 3.68 kW230 V | IP20 | 1.5–2.5 mm² |
| powerCON TRUE1 | EN 60320-1 | 16 A | 3.68 kW230 V | IP65/67 mated | 1.5–2.5 mm² |
| 16 A blue, 2P+E 6h | BS EN IEC 60309-2 | 16 A | 3.68 kW230 V | IP44 or IP67 | 2.5 mm² |
| powerCON original, blue/grey | EN 61984 | 20 A | 4.60 kW230 V | IP20 | 2.5 mm² |
| powerCON 32 A | EN 61984 | 32 A | 7.36 kW230 V | IP20 mated | 4–6 mm² |
| 32 A blue, 2P+E 6h | BS EN IEC 60309-2 | 32 A | 7.36 kW230 V | IP44 or IP67 | 4–6 mm² |
| 63 A blue, 2P+E 6h | BS EN IEC 60309-2 | 63 A | 14.5 kW230 V | IP67 | 16 mm² |
| 125 A blue, 2P+E 6h | BS EN IEC 60309-2 | 125 A | 28.8 kW230 V | IP67 | 35 mm² |
| 16 A red, 3P+N+E 6h | BS EN IEC 60309-2 | 16 A | 11.1 kWthree-phase, 400 V | IP44 or IP67 | 2.5 mm² 5-core |
| 32 A red, 3P+N+E 6h | BS EN IEC 60309-2 | 32 A | 22.2 kWthree-phase, 400 V | IP44 or IP67 | 6 mm² 5-core |
| 63 A red, 3P+N+E 6h | BS EN IEC 60309-2 | 63 A | 43.6 kWthree-phase, 400 V | IP67 | 16 mm² 5-core |
| 125 A red, 3P+N+E 6h | BS EN IEC 60309-2 | 125 A | 86.6 kWthree-phase, 400 V | IP67 | 35 mm² 5-core |
| Powerlock 400 A, five single poles | manufacturer | 400 A | 277.1 kWthree-phase, 400 V | touch-proof caps | single cores, designer sized |
| 16 A yellow, 2P+E 4h | BS EN IEC 60309-2 | 16 A | 1.76 kW110 V | IP44 or IP67 | 2.5 mm² |
| 32 A yellow, 2P+E 4h | BS EN IEC 60309-2 | 32 A | 3.52 kW110 V | IP44 or IP67 | 4–6 mm² |
Three-phase power is √3 × 400 V × I for a balanced load, which is 3.01 times the single-phase figure at the same current, because 400/√3 is 230.9 V rather than 230. Cable sizes are H07RN-F as rental stock usually comes (IEC leads are usually the lighter H05VV-F). Up to 4 mm² they're checked against BS 7671's flexible-cord table (single phase, 30 °C, laid out straight); the bigger sizes are common practice, and the rating for those comes from the cable maker's table for that core count, ambient and installation, so I haven't printed one.
The 13 A plug, and what its fuse is for
13 A × 230 V = 2,990 W
That's the "3 kW" on every drum label and the whole budget for every socket on a multiway. Four sockets on one BS 1363 plug share one 13 A fuse, so an urn and a fan heater on the same block will find the limit before the tea's made.
The fuse in a BS 1363 plug is a BS 1362 cartridge, and it protects the flexible cord between the plug and the kit. It doesn't protect the kit, and it isn't much of an overload device either: summaries of BS 1362 give a 13 A fuse between 1 and 400 seconds to go at 30 A, which is 2.3 times its rating. It's there for the fault that would otherwise set the flex on fire.
The pairing BEAMA publish for which fuse goes with which flex is the clearest proof. Read it against BS 7671's flexible-cord ratings and each fuse turns out to sit with the smallest cord that can carry it:
- 3 A fuse, 0.5 mm² flex. The cord is rated 3 A, the first size in the table at or above 3 A.
- 5 A fuse, 0.75 mm² flex. The cord is rated 6 A, the first size in the table at or above 5 A.
- 13 A fuse, 1.25 mm² flex. The cord is rated 13 A, the first size in the table at or above 13 A.
| BS 1362 | Colour | Status |
|---|---|---|
| 1 A | black | permitted |
| 2 A | black | permitted |
| 3 A | red | preferred |
| 5 A | black | permitted |
| 7 A | black | permitted |
| 10 A | black | permitted |
| 13 A | brown | preferred |
BS 1362 allows any rating up to 13 A. 3 A and 13 A are the preferred values; shops mostly stock 3, 5 and 13, and electrical wholesalers the rest. A 13 A fuse in a plug on 0.5 mm² flex is wrong on paper, though summaries of the guidance say it still clears a short circuit before the cord is badly damaged.
Can a 13 A plug run 13 A all day?
On paper, yes. BS 1363 rates the plug and socket at 13 A and doesn't give a lower continuous figure. The 1995 edition's temperature-rise test, as quoted on the IET's forum, ran at 14 A until the temperature stopped climbing, for up to eight hours. The 2016 revision of BS 1363-2 added an optional EV marking, which means extra cyclic sustained-load tests rather than a different design, because people had started charging cars from ordinary sockets and some of the sockets had cooked.
In practice the rating assumes a clean, tight socket, and a show's 13 A outlets are rarely that. An urn, a heater or a kettle rack pulling 13 A for a whole get-in through a socket with a few thousand insertions behind it is where you find the brown plastic. Anything that needs more than about 10 A for hours belongs on a 16 A blue.
A drum is a 13 A lead only when it's unwound. Coiled, the turns heat each other and the label gives a much lower figure (check the drum; there's no standard number). The volt-drop page has the watts a loom dissipates at full current, which is what's heating the middle of the coil.
BS EN IEC 60309: colour, size and the clock
The round industrial connector is BS EN IEC 60309-2, which replaced BS 4343. Crews call it a commando, after MK's brand, or a Ceeform, after CEE 17, the European spec it grew out of. Three things tell you what one is. The colour says the voltage band. The size says the current: 16, 32, 63 and 125 A bodies are different diameters and don't mate. The earth position, read as an hour on a clock face with the socket's main keyway at six o'clock, says the voltage and frequency again, mechanically.
| Use | Pins | Voltage | Colour | Earth |
|---|---|---|---|---|
| Site tools, centre-tapped earth | 2P+E | 110 V | yellow | 4h |
| Three-phase site supply | 3P+E | 110 V | yellow | 4h |
| Single-phase mains | 2P+E | 230 V | blue | 6h |
| Three-phase with neutral | 3P+N+E | 230/400 V | red | 6h |
| Three-phase, no neutral | 3P+E | 400 V | red | 6h |
| Two phases, no neutral | 2P+E | 400 V | red | 9h |
| North American three-phase | 3P+N+E | 120/208 V | blue | 9h |
| Refrigerated containers | 3P+N+E | 220/380 V | red | 3h |
50 and 60 Hz rows from IEC 60309-2:2023 table 210, as reproduced by MENNEKES. Green connectors with the earth at 10h and 2h are for 100–300 Hz and 300–500 Hz supplies, 12h is a supply from an isolating transformer, and 1h is left free for anything the table doesn't cover.
- Colour is for people. It's chosen by voltage band (yellow 100–130 V, blue 200–250 V, red 300–480 V, line to line on three-phase), which is why North American 120/208 V three-phase is blue, not red. A blue connector tells you the voltage and nothing about the pin count.
- The clock is what stops a plug going in. Within one pin count no two voltages in the table share an hour, so a 2P+E plug for 230 V (6h) can't enter a 2P+E socket wired for 400 V (9h). The build checks that over every row.
- Three-phase with neutral is five pins. 3P+N+E at 6h is the red one you'll see on every distro; 3P+E without the neutral is four pins at the same hour and won't take it.
- Yellow is 110 V centre-tapped earth, 55 V either side of earth, which the construction trade uses for portable tools. A 16 A yellow is 1.76 kW. It turns up on a show through the build crew, and occasionally on a hire company's tools.
| Size | Blue, 230 V | Red, 400 V three-phase | Yellow, 110 V | Sealing you'll meet |
|---|---|---|---|---|
| 16 A | 3.68 kW | 11.09 kW | 1.76 kW | IP44 or IP67 |
| 32 A | 7.36 kW | 22.17 kW | 3.52 kW | IP44 or IP67 |
| 63 A | 14.49 kW | 43.65 kW | 6.93 kW | IP67, often switched and interlocked |
| 125 A | 28.75 kW | 86.60 kW | 13.75 kW | IP67, often switched and interlocked |
- IP44 and IP67. IP44 is splash-proof, with a sprung flap on the socket. IP67 has a gasket and a screw collar, and it's only IP67 with the collar done up or the cap on. The pins and keyway are the same, so the two will usually mate, and the pair is then only as sealed as its weaker half. I haven't found a manufacturer statement on mixed pairs either way.
- 63 A and 125 A: switch off first. Interlocked sockets (IEC 60309-4) won't release the plug while the outlet is live, and won't switch on without a plug in. Some 63 and 125 A connectors also carry a pilot contact that drops the load before the main pins part. Pulling one under load without either draws an arc that can weld the contacts and burn whoever is holding the plug.
IEC 60320: the leads on the back of the kit
The "IEC lead" is a family of appliance couplers in IEC 60320-1, every one rated at 250 V and numbered on a single rule: the connector on the cable has an odd number and the inlet on the kit is one higher. A C13 goes into a C14, a C19 into a C20. The connector is always the female half and the inlet the male, because the end that carries power has to be the one with shrouded contacts.
| Pair | Rating | Earth | Pin temp. | Known as | Where you'll meet it |
|---|---|---|---|---|---|
| C5 / C6 | 2.5 A | earthed | 70 °C | cloverleaf | laptop and projector power bricks |
| C7 / C8 | 2.5 A | none | 70 °C | figure-8 | small players, chargers, some receivers |
| C13 / C14 | 10 A | earthed | 70 °C | "kettle lead", wrongly | most rack kit, desks, computers, moving lights |
| C15 / C16 | 10 A | earthed | 120 °C | the actual kettle lead | kettles, urns, hot kit |
| C17 / C18 | 10 A | none | 70 °C | — | some double-insulated amps and screens |
| C19 / C20 | 16 A | earthed | 70 °C | — | big amps, servers, LED processors, PDUs |
| C21 / C22 | 16 A | earthed | 155 °C | — | rare; very hot kit |
IEC ratings, from IEC 60320-1 as tabulated by Schurter. UL ratings run higher (15 A for a C13, 20 A for a C19) and don't apply here. Pin temperature is the class the coupler is made for: 70 °C "cold", 120 °C "hot", 155 °C "very hot".
- The kettle lead isn't a C13. A kettle's inlet gets hot, so it's a C16, and the lead is a C15, rated for 120 °C pins against the C13's 70 °C. The C15 has a groove that lets it into a C14 as well; the C16 has a ridge that keeps a C13 out. So the C15 from the urn will run your monitor, and the C13 from the monitor won't go into the urn, which is the right way round.
- That's the rule all the shapes follow. A better connector enters a lesser inlet and never the reverse: hotter into cooler, earthed into unearthed. A C13 fits a C18 (an earthed lead on double-insulated kit is harmless), and a C17 won't fit a C14 (an unearthed lead on kit that needs its earth isn't). The build checks every pair in the table against that rule.
- C7/C8, the figure-8, is unearthed at 2.5 A. There's a polarised version with one flat side, which isn't in the standard, and an ordinary C7 goes into a polarised C8 inlet anyway. Don't rely on it for polarity.
- C19/C20 is the 16 A one, and turns up where a C13's 10 A runs out: big amps, LED processors, servers and rack PDUs.
- Locking. An IEC Lock connector grips the earth pin of any standard C14 or C20 inlet and releases with a red slider, so it needs nothing special on the kit. Volex's V-Lock locks with a pin into a notch in a matching V-Lock inlet, so it only locks into kit fitted with one; in an ordinary inlet it's an ordinary connector.
UK leads and their fuses
A moulded lead with a BS 1363 plug carries a BS 1362 fuse sized for its flex, and the coupler on the other end doesn't change that. Cloverleaf leads come on 0.75 mm² with a 3 A fuse. C13 leads come with 5, 10 or 13 A fuses on 0.75 or 1.0 mm²; short leads of up to 2 m are allowed on 0.75 mm² at 10 A. A C19 lead on a 13 A plug is a 13 A lead whatever its 16 A coupler says.
A 13 A fuse ahead of a 10 A C13 leaves the coupler unprotected between 10 and 13 A, the same pattern as the adaptors further down. The fuse is there for the flex under fault, so a rack of C13 kit on one lead wants its sums done against the C13's 10 A rather than the plug's 13.
A C14 is never a power outlet
The male half of any mains connector is for drawing power, never supplying it. When a lead has male pins at the supply end, those pins are live and bare the moment the other end is plugged in, and anyone who touches them gets mains through their hand.
That's why a male-to-male lead (a BS 1363 plug wired to a C14, two 13 A plugs, or any other pairing) must never be made or used. Back-feeding a strip or a PDU through one makes every unused pin on it live as well. Rack PDUs whose outlets look like C13s are female outlets (IEC 60320-2-2 sheet F), and the C14-shaped plug on a jumper lead (sheet E) draws from them, so the male end is still the load end. If a piece of kit seems to need power fed into a male connector, it's been wired wrong.
powerCON: four connectors that look like two
Neutrik's powerCON is the locking mains connector on most lighting and a fair bit of audio. The blue one is power in, the grey one power out, keyed so you can't mate two supplies. That much has stayed the same since the original. What hasn't is the rating and whether you may unplug it live, and the generations look almost identical.
| Family | Certified to | EU rating | Unplug live? | Sealing | Mating cycles | Wire |
|---|---|---|---|---|---|---|
| powerCON, originalNAC3FCA / FCB, NAC3MPA-1 / MPB-1; discontinued | EN 61984 | 20 A | no | IP20 | 1,000 | 2.5 mm² |
| powerCON XXNAC3FXXA-W-S / FXXB, NAC3MPXXA / MPXXB; current | EN 60320-1 | 16 A | only XX to XX | IP20 | 5,000 | 1.5–2.5 mm² |
| powerCON TRUE1, TRUE1 TOPNAC3FX-W, NAC3FX-W-TOP; discontinued, phase out | EN 60320-1 | 16 A | yes | IP65 mated | 5,000 | 1.0–2.5 mm² |
| powerCON TRUE1, currentNAC3F-TRUE1-S; current | EN IEC 60320-1 | 16 A | yes | IP65/IP67 mated or capped | 5,000 | 1.5–2.5 mm² |
| powerCON 32 ANAC3FC-HC; current | EN 61984 | 32 A | no | IP20 mated | 1,000 | 2.5–6 mm² |
From Neutrik's datasheets as served on 3 November 2026. US ratings differ (20 A under the UL standards for the 16 A parts) and aren't shown. The 32 A part's rating holds for an ambient up to 35 °C.
- The newer blue is rated lower than the old one. The original was 20 A under EN 61984, a connector standard, and its datasheet says it "must not be connected or disconnected under load or live". The XX series that replaced it is certified as an appliance coupler under EN 60320-1, at 16 A. That standard is what lets Neutrik claim circuit-breaking capability, and the claim only holds when both the cable connector and the chassis connector are XX.
- So a mixed chain is the worse of both. An original cable into an XX inlet, or the reverse, gives you 16 A (the XX half's rating) and no breaking capacity (the original half's). Treat any chain you haven't checked end to end as that. The part number is the giveaway: XX parts have XX in it.
- TRUE1 is a separate family. It's the weatherproof one, 16 A with breaking capacity and IP65 mated (IP65/IP67 on the current part), and it doesn't mate with blue or grey; the adaptor leads that exist are the evidence. It uses one connector in two genders rather than two keyings, and the female cable connector is the live end. TRUE1 TOP replaced the first TRUE1 and the two are fully compatible; NAC3F-TRUE1-S is now replacing TRUE1 TOP.
- The 32 A powerCON is a bigger body, so it doesn't mate with the 16 or 20 A parts. Neutrik describe it as non-standardised and without breaking capacity, and it takes 2.5 to 6 mm² conductors.
Daisy chains
A powerCON chain is limited by its first link, which carries every fixture downstream of it. At 350 W a unit draws 1.52 A, so a 16 A link carries 10 of them and an old 20 A one 13. The table assumes unity power factor; lower it and the current goes up.
Two things take precedence over the arithmetic. The fixture's manual usually prints a maximum per chain at 230 V, often lower than this because of the fixture's own through wiring or its switch-on surge, and that number wins. And the chain needs protecting at its own rating: a 16 A chain on a 32 A circuit has nothing protecting it between 16 and 32 A.
| Per unit | Current | On 16 A | On 20 A |
|---|---|---|---|
| 100 W | 0.43 A | 36 | 46 |
| 200 W | 0.87 A | 18 | 23 |
| 350 W | 1.52 A | 10 | 13 |
| 500 W | 2.17 A | 7 | 9 |
| 750 W | 3.26 A | 4 | 6 |
| 1200 W | 5.22 A | 3 | 3 |
Units per chain at 230 V and unity power factor, counting the first link's current only. 16 A is XX and TRUE1; 20 A is the original powerCON.
Above 125 A: Powerlock, and the thing it isn't
Generator feeds and main distros use single-pole connectors, one per conductor, five for a three-phase supply with neutral. In the UK that's Powerlock, developed by Litton Veam in the mid-1990s and now an ITT Cannon brand, with compatible parts from other makers. It comes in 400 A and 660 A versions, for up to 1000 V AC. A 400 A three-phase set is 277 kVA, which is 277 kW only at unity power factor. Generators are rated in kVA, and why that number is bigger than the one your kit adds up to is on the power factor and generators page.
- The genders are backwards on purpose. The source has the male pin, shrouded so a finger won't reach it, and the load end has the female. That's the reverse of most power connectors and it's why a dead-looking pin on a Powerlock tail is still not something to hold.
- Colour and keying are separate. The insulators follow the local wiring colours, and each conductor is also keyed mechanically, so a European blue neutral won't mate with a North American blue phase.
- Sequencing. Sequential mating panels make earth and neutral before the phases and break them after. Neither the colours nor the caps do that; the panel does.
- Camlock is the American cousin: single-pole, around 400 A, a twist cam to lock it, without Powerlock's finger-proof shrouds and sequencing. It's not interchangeable, and a hire company's Camlock tails won't go into a UK Powerlock distro.
- Socapex is the other multi-circuit connector you'll meet, six 230 V circuits on one 19-pin plug. Its pinout and what length costs you are on the multipin looms page.
The rules behind it
- BS 7909:2023+A1:2024, Temporary electrical systems for entertainment and related purposes, is the code of practice for the management, design, setting up and operation of a show's power. It replaced BS 7909:2011. It's the usual way an event shows it has met the wiring regulations, and it expects a named person responsible for the system and someone competent to design and sign it off.
- BS 7671:2018+A4:2026, the wiring regulations, has two Part 7 sections that apply. Section 711 covers temporary installations for exhibitions, shows and stands. Section 740 covers temporary installations for structures, amusement devices and booths at fairgrounds, amusement parks and circuses. Amendment 4 was published on 15 April 2026 and Amendment 3 withdrawn six months later. I haven't read A4's text of either section.
- RCDs. Socket-outlets up to 32 A get additional protection by a 30 mA RCD under the general rules, and the exhibitions section extends 30 mA protection to every final circuit for lighting and socket-outlets up to 32 A, emergency lighting excepted (that's IEC 60364-7-711's wording, which section 711 is based on). An RCD protects people from earth faults. It does nothing for an overloaded plug, which is the breaker's and the fuse's job.
Things I keep finding plugged into each other
- A 16 A blue feeding 13 A sockets with no fuse or breaker between. The 16 A breaker upstream lets anything up to 16 A through, so the 13 A socket (or the four of them on a home-made splitter) is protected by nothing between 13 and 16 A. Splitters with a 13 A fuse or MCB in them exist and cost very little more.
- A 13 A plug feeding a 16 A blue socket. The plug fuse does protect it, so this one is safer than it looks, but the socket now offers 2,990 W while looking like 3,680. Plug a 16 A load in and the plug runs over its rating until the fuse decides, which at a bit over double can take minutes. Label it.
- A powerCON chain counted by the fixture, not the first link. See the table above, then check the manual.
- A 16 A chain hung off a 32 A outlet through an adaptor with no 16 A protection. Same problem as the 13 A splitter, one size up.
- Old and new powerCON in one chain, then unplugged live because "powerCON can do that now". The XX half can; the original half can't, and the arc pits the contacts of both.
- A coiled drum at full load. If the thermal cut-out trips, the coil is overheating: unwind the drum fully or use a bigger cable.
- A male-to-male lead, usually made up to back-feed a strip or a PDU. Its free end has live, bare pins. Take it out of service and cut it up.
Your load
Put in a load, per unit, and how many of them share the connector. It works out the current per phase and lists every connector on that supply with the headroom left. Amber is above 80 %, a common planning margin for loads that run all show; BS 7671 doesn't set a flat figure, the designer does. Power factor turns watts into amps: at 0.8 the same watts draw a quarter more current, and the power factor page has why.
This calculator needs JavaScript. The tables above give each connector's power at its rating.
Steady-state current only. Switch-on surges from LED walls, amp racks and anything with a big power supply can trip a breaker that holds all day, which is why big loads go up in sections. Three-phase assumes the load is spread evenly over the phases; an unbalanced one is limited by its busiest phase. A connector's rating is one limit of several: the cable, the breaker and the volt drop all get a say.
Sources
- Neutrik datasheets, downloaded from neutrik.com on 3 November 2026: NAC3FCA and NAC3MPA-1 (the original powerCON, 20 A to EN 61984, the no-breaking-capacity warning), NAC3FXXA-W-S and NAC3MPXXA (powerCON XX, 16 A to EN 60320-1, breaking capability only with XX parts), NAC3FX-W, NAC3FX-W-TOP and NAC3F-TRUE1-S (TRUE1, its successors and their compatibility), and NAC3FC-HC (32 A).
- MENNEKES, Protective conductor contact clock position and plug colours, reproducing IEC 60309-2:2023 table 210, for the earth positions. The voltage-band colours are from the summary of IEC 60309 on Wikipedia, which agrees with the manufacturer catalogues I checked. IEC 60309 itself is paywalled and I haven't read it.
- BS 1363 and BS 1362, worked from summaries (Wikipedia's BS 1363 article for the fuse ratings, colours and BS 1362 pre-arcing times, BSI's catalogue for the current editions). BEAMA's fuse-to-cord pairing and the 14 A temperature-rise test are as quoted on the IET Engineering Communities forum, not read from the standards.
- BS 7671 Table 4F3A, flexible cords, as reproduced in cable makers' catalogues; the IET's announcement of Amendment 4 (15 January 2026); and IEC 60364-7-711 for the 30 mA wording.
- BS 7909:2023+A1:2024, BSI catalogue entry, for the edition and scope.
- Powerlock: Wikipedia's article and the ITT Veam material it cites, for the ratings, history, reversed genders, keying and sequencing.
- Van Damme's TRUE1 cable listing and LEX Products' grey-to-TRUE1 adaptor, for TRUE1 not mating with blue/grey powerCON.
- IEC 60320: Schurter's appliance-coupler knowledge pages and white paper for the ratings and pin-temperature classes, and Wikipedia's IEC 60320 article for which connector enters which inlet, the polarised C7 and the 2-2 interconnection sheets. IEC Lock from UK distributors' listings (Canford and others); V-Lock from Volex and Schurter. UK lead fusing from retailers' listings and the IET forum. The standard itself is paywalled and I haven't read it.
Assembled 3 November 2026 with AI assistance. The arithmetic is checked at build time (the kilowatts, the fuse-to-cord pairing against Table 4F3A, the colour of every IEC 60309 row against its voltage band, the clock positions within each pin count, and the powerCON ratings) and those checks catch a transcription error but can't catch a wrong source. The Neutrik figures are read from current datasheets; the British and IEC standards are paywalled and are worked from reproductions, so check anything you're relying on against your own copy. None of this is a design. A temporary installation needs designing, inspecting and signing off by a competent person under BS 7909.
Companion pages: cable voltage drop for what a long feed loses and how hot it gets, multipin looms for Socapex, power factor and generators for kVA, kW and sizing the thing at the end of the Powerlock, and LED processor and power lines for how many panels go on a 16 A circuit.